Permit Details

Status:
C of o
Type:
COMMERCIAL OTHER
Address NEW:
1097 W PRINCE RD 03
Apply Date:
12/09/2009
Applicant:
CONWAY STONE & TILE
Description:
C OF O:TILE SALES

Permit Reviews

Permit Number - T09OT02651
Permit Status: C of o
Permit Description: C OF O:TILE SALES
Start Date Submittal Complete Date Status  
12/09/2009 C OF O 12/09/2009 COMPLETED Review Details
12/29/2009 C OF O 01/04/2010 COMPLETED Review Details

Completed Inspections

Permit Status: C of o
Permit Number: T09OT02651
Permit Description: C OF O:TILE SALES
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/17/2009 CERTIFICATE OF OCCUPANCY AQUIROZ Approved IVRS - Inspection :*
1) NEED LEVER HANDLES ON RESTROOM DOORS
2) NEED GRAB BARS IN RESTROOMS
3) NEED SIGNAGE AT RESTROOMS
4) FLUSH HANDLE NEEDS TO BE ON WIDE SIDE OF RESTROOM
5) LOWER LAV TO 34" MAX IN RESTROOM
6) NEED INSULATION KITS AT TRAPS UNDER LAV
7) PLUG EMPTY BREAKER PANEL
8) PLUG ALL PLUMBING PIPES NOT IN USE
9) INSTALL ANTI-SIPHON ON ALL EXTERIOR HOSE BIBS
10) PROVIDE SIGN ABOVE DOORS "TO REMAIN UNLOCKED DURING WORKING HOURS"
11) PROVIDE THUMB LATCH LOCKS ON DOORS
12) NEED C OF O FIRE APPROVAL
13) REMOVE BOLT LATCHES FROM DOORS
12/17/2009 FIRE - FINAL DRamirez Approved Not approved 12/17/09.
1.) Need a sign over the main exit door reading,"DOOR MUST REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED".
2.) Occupant loads of over 49 people require a minimum of 2 exits (occupant load is 80)
3.) Need illuminated exit signs for both required exits.Lights must be illuminated at all times.
4.) Need emergency back-up lighting for both exits.
5.) The security doors must open in the same direction of egress travel.
6.) Need a breaker blank in the electrical panel.
7.) Cover opening in the wall. (center room)
8.) The smoke detector in back room needs a battery.
9.) Missing cover plate.(back room)
10.) Portable fire extinghuishers must be inspected and serviced annually.(non-required fire exinghuishers can be removed from service)
11.) Remove keyed lock from 2nd. exit door. Replace with thumb-turn lock.
12.) Need directional signs directing to secondary exit.
13.) Need approved, updated floor plans.

Documents

File Name Document Type  
C OF O_06-23-2010.TIF CERT OF OCC VIEW
SITE PLAN 01-04-2010.TIF CERT OF OCC VIEW
SITE DEPICTION_08-03-2010.TIF CERT OF OCC VIEW
FLOOR PLAN_06-09-2010.TIF CERT OF OCC VIEW