Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SIGN PERMIT
Apply Date:
05/21/2009
Applicant:
COOK & CO SIGNMAKERS INC , *C
Description:
16698
Contractors:
  • COOK & CO SIGNMAKERS INC , *C

Outstanding Inspections

Permit Status: Expired
Permit Number: T09OT01023
Permite Description: 16698
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/18/2009 SIGN ELECTRIC N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECTING MEANS TO BE LOCKABLE WHEN NOT WITHIN SIGHT OF SIGN
2) STRAP EMT WITHIN 3' OF CONNECTIONS
3) CLOSE OPEN JUNCTION BOX
4) SERVICE LIGHT TO BE INSTALLED AT EQUIPMENT TO BE SERVED AND SWITCH TO BE AT ENTRY POINT
5) NEED TO RUN EQUIPMENT GROUNDS TO BOND METAL PARTS OF SIGN

Completed Inspections

Permit Status: Expired
Permit Number: T09OT01023
Permit Description: 16698
Total Completed Inspections - 2
Date Description Inspector Results Comments
06/01/2009 SIGN SITE REVIEW HTHRALL Approved CUSTOMER EMAILED PICTURE SHOWING DOOR SIGN DOWN. OKAY TO PROCEED WITH PERMITTING THE NEW PROJECT.
08/19/2009 SIGN INSPECTION JYBARRA Approved IVRS - Inspection :*

Documents

File Name Document Type  
None SIGNS VIEW