Permit: T09OT01023

Parcel: 13355230A


Addresses:

9565 E 22ND ST #149


Inspection Status: Denied

Inspection History: SIGN ELECTRIC

Permit Number - T09OT01023

Inspection Description - SIGN ELECTRIC

Inspection Status - Denied

Date Description Inspector Results Comments
09/18/2009 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECTING MEANS TO BE LOCKABLE WHEN NOT WITHIN SIGHT OF SIGN
2) STRAP EMT WITHIN 3' OF CONNECTIONS
3) CLOSE OPEN JUNCTION BOX
4) SERVICE LIGHT TO BE INSTALLED AT EQUIPMENT TO BE SERVED AND SWITCH TO BE AT ENTRY POINT
5) NEED TO RUN EQUIPMENT GROUNDS TO BOND METAL PARTS OF SIGN
08/19/2009 SIGN ELECTRIC Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
1) CALLED SIGN CONTRACTOR GAVE 60-MINUTE NOTICE. WAITED 15 MINUTES PAST SCHEDULED MEET TIME
2) NEED TO RECALL AND HAVE PLANS ON SITE AND PROVIDE ACCESS TO EQUIPMENT