09/18/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DISCONNECTING MEANS TO BE LOCKABLE WHEN NOT WITHIN SIGHT OF SIGN 2) STRAP EMT WITHIN 3' OF CONNECTIONS 3) CLOSE OPEN JUNCTION BOX 4) SERVICE LIGHT TO BE INSTALLED AT EQUIPMENT TO BE SERVED AND SWITCH TO BE AT ENTRY POINT 5) NEED TO RUN EQUIPMENT GROUNDS TO BOND METAL PARTS OF SIGN |
|
08/19/2009 | SIGN ELECTRIC | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1) CALLED SIGN CONTRACTOR GAVE 60-MINUTE NOTICE. WAITED 15 MINUTES PAST SCHEDULED MEET TIME 2) NEED TO RECALL AND HAVE PLANS ON SITE AND PROVIDE ACCESS TO EQUIPMENT |