Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address:
432 W PRINCE RD
Address NEW:
432 W PRINCE RD
Apply Date:
03/12/2009
Applicant:
ERIC WOON
Description:
C OF O:RETAIL

Permit Reviews

Permit Number - T09OT00514
Permit Status: Closed
Permit Description: C OF O:RETAIL
Start Date Submittal Complete Date Status  
03/12/2009 C OF O 03/12/2009 COMPLETED Review Details

Outstanding Inspections

Permit Status: Closed
Permit Number: T09OT00514
Permite Description: C OF O:RETAIL
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
03/13/2009 CERTIFICATE OF OCCUPANCY N/A Not ready for Inspection IVRS - Inspection :*
1. NEED FIRE FINAL
2. UNI-SEX RESTROOM SIGN (NOT ADA APPLICATION)
3. EXTERIOR HOSE BIBS NEED ANTI-SIPHON DEVICES
03/13/2009 FIRE - FINAL N/A Denied 1.) Remove all cube adaptors. Only adaptors allowed are ones that are grounded, polarizerd have a reset and have surge protection.
2.) Provide a thumb-turn lock on the west door leading into the office from the break room.
3.) Replace missing or broken cover plates thru-out building.
4.) Provide Exit sign over East door leading into office from break room.
5.) Provide a sign on double doors leading into shop area reading "NOT AN EXIT".
6.) Remove "cross-bar security system"form rear exit door.Provide thumb-turn lock.
7.) Remove Exit sign from door leading into storage room.
8.) Thumb-turn lock on insde of door leading out of storage room.
9.) Provide a sign over door leading from shop area into office are that reads "NOT AN EXIT".
10. Portable fire extinguishers are dur for servicing.

Documents

File Name Document Type  
None DOCUMENTS VIEW