Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2009 | FIRE - FINAL | Denied | 1.) Remove all cube adaptors. Only adaptors allowed are ones that are grounded, polarizerd have a reset and have surge protection. 2.) Provide a thumb-turn lock on the west door leading into the office from the break room. 3.) Replace missing or broken cover plates thru-out building. 4.) Provide Exit sign over East door leading into office from break room. 5.) Provide a sign on double doors leading into shop area reading "NOT AN EXIT". 6.) Remove "cross-bar security system"form rear exit door.Provide thumb-turn lock. 7.) Remove Exit sign from door leading into storage room. 8.) Thumb-turn lock on insde of door leading out of storage room. 9.) Provide a sign over door leading from shop area into office are that reads "NOT AN EXIT". 10. Portable fire extinguishers are dur for servicing. |