Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
4566 E PATRICIA ST
Apply Date:
12/17/2009
Applicant:
SOLAR STORE L L C *C
Description:
REPLACE: HVAC
Contractors:
  • ALPINE HEATING AND COOLING L L C

Permit Reviews

Permit Number - T09ME00804
Permit Status: Expired
Permit Description: REPLACE: HVAC
Start Date Submittal Complete Date Status  
12/17/2009 MECHANICAL 12/17/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09ME00804
Permit Status: Expired
Permit Description: REPLACE: HVAC
Total Outstanding Activity Conditions - 1
Date Name
12/17/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09ME00804
Permite Description: REPLACE: HVAC
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/18/2009 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE ELECTRIC CIRCUITS FOR FAN COIL AND CONDENSOR MUST BE SEPERATE
2) CONDENSATE TRAP APPEARS TO BE INSTALLED BACKWARDS
3) USE PURPLE PRIMER ON ALL PVC PRIOR TO GLUE
4) CONNECT THE OVERFLOW SENSOR ON CONDENSATE PUMP AND PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON EVAP COIL
5) MAKR THE FAN COIL DATA PLATE WITH PROPER HEAT STRIP INSTALLED
6) INSULATE THE SHEET METAL SLEEVE ON FAN COIL
7) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
8) DO NOT HAVE RUBBER HOSE EXPOSED OUTDOORS. USE COPPER TUBING AND SUPPORT EVERY 4'
9) 30 AMP FUSES NOT ADEQUATE FOR CONDENSOR
10) LOW VOLTAGE WIRE MUST BE IN CONDUIT
11) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
12) PROVIDE A MEYERS HUB TYPE FITTING AT CONDUIT CONNECTION TO CIRCUIT PANEL
13) ID BREAKER FO CONDENSOR
12/18/2009 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*

Documents

File Name Document Type  
None CONSTRPLANS VIEW
None DOCUMENTS VIEW