Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09ME00804
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE ELECTRIC CIRCUITS FOR FAN COIL AND CONDENSOR MUST BE SEPERATE 2) CONDENSATE TRAP APPEARS TO BE INSTALLED BACKWARDS 3) USE PURPLE PRIMER ON ALL PVC PRIOR TO GLUE 4) CONNECT THE OVERFLOW SENSOR ON CONDENSATE PUMP AND PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON EVAP COIL 5) MAKR THE FAN COIL DATA PLATE WITH PROPER HEAT STRIP INSTALLED 6) INSULATE THE SHEET METAL SLEEVE ON FAN COIL 7) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 8) DO NOT HAVE RUBBER HOSE EXPOSED OUTDOORS. USE COPPER TUBING AND SUPPORT EVERY 4' 9) 30 AMP FUSES NOT ADEQUATE FOR CONDENSOR 10) LOW VOLTAGE WIRE MUST BE IN CONDUIT 11) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 12) PROVIDE A MEYERS HUB TYPE FITTING AT CONDUIT CONNECTION TO CIRCUIT PANEL 13) ID BREAKER FO CONDENSOR |