Permit: T09ME00804

Parcel: 110053590


Addresses:

4566 E PATRICIA ST


Inspection Status: Denied

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09ME00804

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
12/18/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE ELECTRIC CIRCUITS FOR FAN COIL AND CONDENSOR MUST BE SEPERATE
2) CONDENSATE TRAP APPEARS TO BE INSTALLED BACKWARDS
3) USE PURPLE PRIMER ON ALL PVC PRIOR TO GLUE
4) CONNECT THE OVERFLOW SENSOR ON CONDENSATE PUMP AND PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON EVAP COIL
5) MAKR THE FAN COIL DATA PLATE WITH PROPER HEAT STRIP INSTALLED
6) INSULATE THE SHEET METAL SLEEVE ON FAN COIL
7) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
8) DO NOT HAVE RUBBER HOSE EXPOSED OUTDOORS. USE COPPER TUBING AND SUPPORT EVERY 4'
9) 30 AMP FUSES NOT ADEQUATE FOR CONDENSOR
10) LOW VOLTAGE WIRE MUST BE IN CONDUIT
11) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
12) PROVIDE A MEYERS HUB TYPE FITTING AT CONDUIT CONNECTION TO CIRCUIT PANEL
13) ID BREAKER FO CONDENSOR