Permit: T09ME00746
Permit Details
Apply Date:
11/24/2009
Applicant:
TANYA WINTER
Description:
HOOD:SAFETY INSPECTION
Permit Reviews
Permit Number - T09ME00746
Permit Status: Expired
Permit Description: HOOD:SAFETY INSPECTION
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
11/24/2009 | MECHANICAL | 11/24/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09ME00746
Permit Status: Expired
Permit Description: HOOD:SAFETY INSPECTION
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/24/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09ME00746
Permite Description: HOOD:SAFETY INSPECTION
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2009 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONTINOUSLY WELDED 16 GA. GREASE DUCT UP TO FAN CONNECTION 2) PROVIDE GREASE RECEPTORS UNDER HOOD AND ON ROOF 3) PROVIDE APPROVED FITTINGS 4) PROVIDE APPROVED LIGHTING UNDER HOOD (NO CONDUIT WITHIN HOOD) 5) ALL EQUIPMENT TO BE WITHIN 6" OF OUTER EDGE OF HOOD AND NOT TO EXCEED 48" BELOW 6) PROVIDE APPROVED FLEX CONNECTOR ON GREASE DUCT 7) EXHAUST FAN AND MAKE UP AIR TO BE INTERLOCKED |