Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09ME00746

Parcel: 124061720


Addresses:

136 N PARK AV


Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T09ME00746

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
11/30/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE CONTINOUSLY WELDED 16 GA. GREASE DUCT UP TO FAN CONNECTION
2) PROVIDE GREASE RECEPTORS UNDER HOOD AND ON ROOF
3) PROVIDE APPROVED FITTINGS
4) PROVIDE APPROVED LIGHTING UNDER HOOD (NO CONDUIT WITHIN HOOD)
5) ALL EQUIPMENT TO BE WITHIN 6" OF OUTER EDGE OF HOOD AND NOT TO EXCEED 48" BELOW
6) PROVIDE APPROVED FLEX CONNECTOR ON GREASE DUCT
7) EXHAUST FAN AND MAKE UP AIR TO BE INTERLOCKED
11/25/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THERE IS NO ADDRESS 136 N PARK POSTED ON ANY BLDG IN THIS AREA
2) DOORS LOCKED
3) MESSAGE BLANK