Permit: T09ME00546
Permit Details
Apply Date:
08/26/2009
Applicant:
WATSON REFRIGERATION COMPANY INC
Description:
REPL 3 TON SPLIT SYSTEM (APA)
Contractors:
- WATSON REFRIGERATION COMPANY INC
Outstanding Activity Conditions
Permit Number - T09ME00546
Permit Status: Final
Permit Description: REPL 3 TON SPLIT SYSTEM (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/26/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09ME00546
Permit Description: REPL 3 TON SPLIT SYSTEM (APA)
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2009 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) PROVIDE INSULATION ON EXPOSED SHEET METAL DUCT IN FURNACE ROOM 2) PROVIDE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) PROVIDE A HOSE CLAMP ON PUMP 4) PROVIDE A GFI SERVICE RECEPTACLE WITHIN 25' OF CONDENSOR 5) SECURE COPPER DRAIN LINE AND ISOLATE FROM STEEL. SUPPORT EVERY 6' ON ROOF AND TERMINATE TO THE GROUND |
| 01/22/2010 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
| 01/25/2010 | PERMIT FINALED | JWEATHER | Approved |