Permit: T09ME00189
Permit Details
Apply Date:
05/02/2009
Applicant:
WALTER VIRGINIA
Description:
Replacing existing 2.5ton package heat pump. Roof mounted.
Contractors:
- RITEWAY VENTILATING CO. *C*
Outstanding Activity Conditions
Permit Number - T09ME00189
Permit Status: Expired
Permit Description: Replacing existing 2.5ton package heat
pump. Roof mounted.
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/02/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09ME00189
Permite Description: Replacing existing 2.5ton package heat
pump. Roof mounted.
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2009 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
05/27/2009 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC UNIT ON ROOF IS OVERFUSED MAX IS 30 AMP. FUSES ARE 40 AMP. ALSO, THERE IS A FUSE BLOCK FOR A HEAT STRIP BUT THE STRIP IS NOT MARKED ON THE UNIT DATA PLATE. 2. PROVIDE CITY APPROVED LOAD CALC. FOR RTU |