Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
05/02/2009
Applicant:
WALTER VIRGINIA
Description:
Replacing existing 2.5ton package heat pump. Roof mounted.
Contractors:
  • RITEWAY VENTILATING CO. *C*

Outstanding Activity Conditions

Permit Number - T09ME00189
Permit Status: Expired
Permit Description: Replacing existing 2.5ton package heat pump. Roof mounted.
Total Outstanding Activity Conditions - 1
Date Name
05/02/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09ME00189
Permite Description: Replacing existing 2.5ton package heat pump. Roof mounted.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
05/27/2009 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/27/2009 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AC UNIT ON ROOF IS OVERFUSED MAX IS 30 AMP. FUSES
ARE 40 AMP. ALSO, THERE IS A FUSE BLOCK FOR A HEAT STRIP BUT THE STRIP IS NOT MARKED ON THE UNIT DATA PLATE.
2. PROVIDE CITY APPROVED LOAD CALC. FOR RTU

Documents

File Name Document Type  
None DOCUMENTS VIEW