Permit: T09ME00189

Parcel: 116185030

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T09ME00189

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
05/27/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AC UNIT ON ROOF IS OVERFUSED MAX IS 30 AMP. FUSES
ARE 40 AMP. ALSO, THERE IS A FUSE BLOCK FOR A HEAT STRIP BUT THE STRIP IS NOT MARKED ON THE UNIT DATA PLATE.
2. PROVIDE CITY APPROVED LOAD CALC. FOR RTU