Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC UNIT ON ROOF IS OVERFUSED MAX IS 30 AMP. FUSES ARE 40 AMP. ALSO, THERE IS A FUSE BLOCK FOR A HEAT STRIP BUT THE STRIP IS NOT MARKED ON THE UNIT DATA PLATE. 2. PROVIDE CITY APPROVED LOAD CALC. FOR RTU |