Permit: T09ME00016
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
820 E FORT LOWELL RD
Address NEW:
820 E FORT LOWELL RD
Apply Date:
01/13/2009
Applicant:
WALTER VIRGINIA
Description:
Replace 2-5 ton split systems (hybrid heat: gas heating w/ electric backup).
Contractors:
- RITEWAY VENTILATING CO. *C*
Outstanding Activity Conditions
Permit Number - T09ME00016
Permit Status: Expired
Permit Description: Replace 2-5 ton split systems (hybrid
heat: gas heating w/ electric backup).
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/13/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09ME00016
Permite Description: Replace 2-5 ton split systems (hybrid
heat: gas heating w/ electric backup).
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 01/22/2009 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE R-8 INSULATION ON DUCT IN MECH. ROOM 2. FLUE CONDUCTOR PIPE CANNOT RUN AT AN ANGLE IN EXCESS OF 60 DEG. 3. FLUE CONDUCTOR PIPE CANNOT BE INSTALLED WITHIN 6" OF COMBUSTIBLE MATERIAL 4. PER SECTION 304.10 GUARDS MUST BE PROVIDED ON ANY SERVICABLE EQUIPMENT WITHIN 10' OF ROOF EDGE 5. NO LADDER PROVIDED FOR ROOFTOP INSPECTION |