Permit: T09ME00016

Parcel: 11308002A

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/22/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE R-8 INSULATION ON DUCT IN MECH. ROOM
2. FLUE CONDUCTOR PIPE CANNOT RUN AT AN ANGLE IN EXCESS OF 60 DEG.
3. FLUE CONDUCTOR PIPE CANNOT BE INSTALLED WITHIN 6" OF COMBUSTIBLE MATERIAL
4. PER SECTION 304.10 GUARDS MUST BE PROVIDED ON ANY SERVICABLE EQUIPMENT WITHIN 10' OF ROOF EDGE
5. NO LADDER PROVIDED FOR ROOFTOP INSPECTION