Permit: T09EL02629
Permit Details
Apply Date:
12/02/2009
Applicant:
DANIEL YURKIEVICH
Description:
UPGRADE:ELECTRIC 200AMP
Outstanding Activity Conditions
Permit Number - T09EL02629
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/02/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T09EL02629
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2010 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MIN POINT OF ATTACHMENT FOR SERVICE CONDUCTORS TO BE 10' MIN ABOVE 2) MIN CLEARANCE ON SERVICE CONDUCTORS TO BE 12' ABOVE GRADE 3) BOND GAS AND WATER PIPING 4) NEED PROTECTIVE BUSHING AT WIRE ENTRY OF SEAL OPENING WITH NON COMBUSTIBLE MATERIAL 5) 120V BRANCH CIRCUITS REQUIRE INSULATED NEUTRAL CONDUCTOR. CHECK BRANCH CIRCUIT WIRING 6) CHECK GROUND CLAMPS LISTED FOR DIRECT BURY AND FOR USE ON GROUND RODS 7) INSTALL ROOF JACK ON SERVICE RACEWAY |
| 01/13/2010 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |