Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Withdrwn
Type:
SINGLE FAMILY OTHER
Address:
334 E 23RD ST
Address NEW:
334 E 23RD ST
Apply Date:
12/02/2009
Applicant:
DANIEL YURKIEVICH
Description:
UPGRADE:ELECTRIC 200AMP

Outstanding Activity Conditions

Permit Number - T09EL02629
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
Date Name
12/02/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Withdrwn
Permit Number: T09EL02629
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
01/13/2010 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MIN POINT OF ATTACHMENT FOR SERVICE CONDUCTORS TO BE 10' MIN ABOVE
2) MIN CLEARANCE ON SERVICE CONDUCTORS TO BE 12' ABOVE GRADE
3) BOND GAS AND WATER PIPING
4) NEED PROTECTIVE BUSHING AT WIRE ENTRY OF SEAL OPENING WITH NON COMBUSTIBLE MATERIAL
5) 120V BRANCH CIRCUITS REQUIRE INSULATED NEUTRAL CONDUCTOR. CHECK BRANCH CIRCUIT WIRING
6) CHECK GROUND CLAMPS LISTED FOR DIRECT BURY AND FOR USE ON GROUND RODS
7) INSTALL ROOF JACK ON SERVICE RACEWAY
01/13/2010 ELECTRIC - FINAL N/A Denied IVRS - Inspection :