Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MIN POINT OF ATTACHMENT FOR SERVICE CONDUCTORS TO BE 10' MIN ABOVE 2) MIN CLEARANCE ON SERVICE CONDUCTORS TO BE 12' ABOVE GRADE 3) BOND GAS AND WATER PIPING 4) NEED PROTECTIVE BUSHING AT WIRE ENTRY OF SEAL OPENING WITH NON COMBUSTIBLE MATERIAL 5) 120V BRANCH CIRCUITS REQUIRE INSULATED NEUTRAL CONDUCTOR. CHECK BRANCH CIRCUIT WIRING 6) CHECK GROUND CLAMPS LISTED FOR DIRECT BURY AND FOR USE ON GROUND RODS 7) INSTALL ROOF JACK ON SERVICE RACEWAY |