Permit: T09EL02618
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
6509 E CALLE BOOTIS
Address NEW:
6509 E CALLE BOOTIS
Apply Date:
12/01/2009
Applicant:
MANDY SPROUL ***C
Description:
RECONNECT: ELECTRIC
Outstanding Activity Conditions
Permit Number - T09EL02618
Permit Status: Final
Permit Description: RECONNECT: ELECTRIC
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/01/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09EL02618
Permit Description: RECONNECT: ELECTRIC
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | ELECTRIC - RECONNECT | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. KITCHEN COUNTER RECEPTACLES TO BE GFCI PROTECTED 2. INSTALL MISSING WALL PLATES 3. INSTALL SMOKE DETECTORS IN BEDROOMS & HALL PER INSTRUCTIONS. 4. BLANK OPEN CEILING JUNCTION BOX BEDROOM 5. INSTALL FULL 3/4" T&P LINE @ WATER HEATER, LINE TO BE SLOPED TO DRAIN. 6. BLANK OPEN CEILING JUNCTION BOX ARIZONA ROOM 7. REMOVE NON-CODE COMPLIANT CORD FROM PANEL TO RECEPTACLE ABOVE BACK DOOR 8. SEAL OPEN KNOCK OUTS IN PANEL 9. LABEL BREAKERS IN PANELS 10. VERIFY GROUNDING TYPE RECEPTACLES HAVE EQUIPMENT GROUNDED 11. RESCHEDULE WHEN COMPLETE |
| 12/03/2009 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 03/15/2010 | TEP CLEARANCE - PM | JWEATHER | Approved | RECN CLEARED PER J. MILITELLO |
| 03/16/2010 | PERMIT FINALED | JWEATHER | Approved |