Permit: T09EL02618

Parcel: 135021710


Addresses:

6509 E CALLE BOOTIS

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
03/15/2010 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
03/11/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
12/03/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. KITCHEN COUNTER RECEPTACLES TO BE GFCI PROTECTED
2. INSTALL MISSING WALL PLATES
3. INSTALL SMOKE DETECTORS IN BEDROOMS & HALL PER INSTRUCTIONS.
4. BLANK OPEN CEILING JUNCTION BOX BEDROOM
5. INSTALL FULL 3/4" T&P LINE @ WATER HEATER, LINE TO BE SLOPED TO DRAIN.
6. BLANK OPEN CEILING JUNCTION BOX ARIZONA ROOM
7. REMOVE NON-CODE COMPLIANT CORD FROM PANEL TO RECEPTACLE ABOVE BACK DOOR
8. SEAL OPEN KNOCK OUTS IN PANEL
9. LABEL BREAKERS IN PANELS
10. VERIFY GROUNDING TYPE RECEPTACLES HAVE EQUIPMENT GROUNDED
11. RESCHEDULE WHEN COMPLETE