Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
7120 E BROADWAY BL
Apply Date:
08/28/2009
Applicant:
BERT S ELECTRIC AND PLUMBING CO;*C
Description:
MINOR ELECTRICAL CIRCUIT REPAIR (APA)
Contractors:
  • BERT S ELECTRIC AND PLUMBING CO;*C

Outstanding Activity Conditions

Permit Number - T09EL01987
Permit Status: Final
Permit Description: MINOR ELECTRICAL CIRCUIT REPAIR (APA)
Total Outstanding Activity Conditions - 1
Date Name
08/28/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09EL01987
Permit Description: MINOR ELECTRICAL CIRCUIT REPAIR (APA)
Total Completed Inspections - 5
Date Description Inspector Results Comments
08/31/2009 ELECTRIC - FINAL RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR CUT AND STOLEN. REPAIR OR REPLACE GROUNDING ELECTRODE SYSTEM. BOND GAS AND WATER PIPING
2) SERVICE DISCONNECTS MISSING MAIN BONDING JUMPERS
3) MARK ALL SERVICE DISCONNECTS
4) HAVE MC CABLE HANGING IN DINING ROOM. REMOVE OR MAKE SAFE
5) DISCONNECT AND REMOVE OLD WIRING TO SPRINKLER SYSTEM CONTROLLER NOT BEING USED
6) NEED TO HAVE DNR REPORT ON SITE
7) HAVE ELECTRICAL CONTRACTOR SUBMIT LETTER ON COMPANY LETTER HEAD WITH SIGNATURE STATING ALL CHECKS AND REPAIRS THAT HAVE BEEN DONE
8) ADD ELECTRIC RECONNECT TO PERMIT
9) HAVE ELECTRICAL CONTRACTOR CHECK WIRING AT SERVICE. IT APPEARS THAT CONDUCTOR INSULATION MAY BE DAMAGED TO OVER HEATING AND NEEDS TO BE REPLACED
01/27/2010 TEP CLEARANCE - AM JWEATHER Approved RECN CLEARED PER R. HOLLANDER
02/05/2010 ELECTRIC - RECONNECT RJIROUDE Approved IVRS - Inspection :*
02/23/2010 FIRE - FINAL DRamirez Approved Approved 2/23/10
03/19/2010 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW