Permit: T09EL01987

Parcel: 13419042A


Addresses:

7120 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01987

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) RECEIVED LETTER FOR WORK COMPLETED FROM ELECTRICAL CONTRACTOR
01/26/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH ITEM 2,6 AND 7 FROM 1ST INSPECTION
2) CHECK NEW WORK TO ANSUL SYSTEM
01/25/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/20/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
2) EXPOSE GROUNDING ELECTRODE SYSTEM
3) OPEN CUTLER
4) INSTALL NEUTRAL CONDCUTORS TO ALL SERVICE DISCONNECTS
5) GROUND ELECTRODE CONDUCTOR RUN IN METAL RACEWAY TO BE BONDED AND RACEWAY AT BOTH ENDS
08/31/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR CUT AND STOLEN. REPAIR OR REPLACE GROUNDING ELECTRODE SYSTEM. BOND GAS AND WATER PIPING
2) SERVICE DISCONNECTS MISSING MAIN BONDING JUMPERS
3) MARK ALL SERVICE DISCONNECTS
4) HAVE MC CABLE HANGING IN DINING ROOM. REMOVE OR MAKE SAFE
5) DISCONNECT AND REMOVE OLD WIRING TO SPRINKLER SYSTEM CONTROLLER NOT BEING USED
6) NEED TO HAVE DNR REPORT ON SITE
7) HAVE ELECTRICAL CONTRACTOR SUBMIT LETTER ON COMPANY LETTER HEAD WITH SIGNATURE STATING ALL CHECKS AND REPAIRS THAT HAVE BEEN DONE
8) ADD ELECTRIC RECONNECT TO PERMIT
9) HAVE ELECTRICAL CONTRACTOR CHECK WIRING AT SERVICE. IT APPEARS THAT CONDUCTOR INSULATION MAY BE DAMAGED TO OVER HEATING AND NEEDS TO BE REPLACED