Permit: T09EL01832
Permit Details
Apply Date:
08/10/2009
Applicant:
DAWSON ELECTRIC L L C
Description:
REPLACE: ELECTRICAL PANEL 200AMP
Contractors:
- DAWSON ELECTRIC L L C
Outstanding Activity Conditions
Permit Number - T09EL01832
Permit Status: Expired
Permit Description: REPLACE: ELECTRICAL PANEL 200AMP
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/10/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09EL01832
Permite Description: REPLACE: ELECTRICAL PANEL 200AMP
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2009 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED PREVIOUS WRITE-UP ON SITE 2) BOND GUTTER ENCLOSURE 3) PANEL LABELING TO BE AS PER 408.4-NO ABBREVIATIONS OR GENERAL LABELING 4) MAINTAIN WORKING CLEARANCES 110.26-REMOVE VEGITATION 5) ANCHOR RISER STRUT ABOVE PANEL |
Completed Inspections
Permit Status: Expired
Permit Number: T09EL01832
Permit Description: REPLACE: ELECTRICAL PANEL 200AMP
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. MORENO |