Permit: T09EL01832

Parcel: 117033380


Addresses:

502 E UNIVERSITY BL


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01832

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED PREVIOUS WRITE-UP ON SITE
2) BOND GUTTER ENCLOSURE
3) PANEL LABELING TO BE AS PER 408.4-NO ABBREVIATIONS OR GENERAL LABELING
4) MAINTAIN WORKING CLEARANCES 110.26-REMOVE VEGITATION
5) ANCHOR RISER STRUT ABOVE PANEL
08/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED GROUNDING STRAPPED TO WALL
2) NEDD PEG BUSHING FOR NIPPLE IN GUTTER
3) NEED LOCK NUTS WITHOUT SEALS