Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
7540 E 27TH ST
Address NEW:
7540 E 27TH ST
Apply Date:
08/05/2009
Applicant:
N/A
Description:
UPGRADE: ELECTRIC 200 AMP
Contractors:
  • MAJOR ELECTRIC INC,*C

Permit Reviews

Permit Number - T09EL01805
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC 200 AMP
Start Date Submittal Complete Date Status  
08/05/2009 ELECTRICAL 08/05/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09EL01805
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
08/05/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09EL01805
Permit Description: UPGRADE: ELECTRIC 200 AMP
Total Completed Inspections - 3
Date Description Inspector Results Comments
08/20/2009 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. JIROUDEK
09/01/2009 ELECTRIC - SERVICE UPGRADE RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) CONNECT EQUIPMENT GROUND TO JUNCTION BOX
2) SEAL OPENING IN BACK OF JUNCTION BOX WITH NON-COMBUSTIBLE MATERIAL
3) HAVE EXPOSED CONDUCTOR AT TERMINATIONS IN JUNCTION BOX
4) HAVE SPLICED DISSIMILAR METALS COPPER AND ALUMINUM
5) REMOVE TEMP RECEPTACLE
6) COMPLETE PREVIOUS INSPECTION ITEM #2 AND VERIFY PIPE FILL
11/25/2009 ELECTRIC - FINAL RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS AND EMT TO COMPLETELY SEAL INTO CONDUCTORS AND COUPLINGS
2) EQUIPMENT GROUNDS AND NEUTRALS TO BE SEPERATE AT SUB PANEL
3) CONNECT EQUIPMENT GROUND BAR TO PANEL ENCLOSURE AT SUB PANEL
4) SEAL OPENING AT WIRE ENTRY WITH NON COMBUSTIBLE MATERIAL AT BACK OF SUB PANEL
5) CHECK ALL WIRE TERMINATIONS TIGHTENED PER MANUFACTURES REQUIREMENT
6) #8 AL GOOD FOR 30 AMP ONLY
7) 1 1/4" EMT NOT SIZED PROPERLY FOR 4-1/0 XHHW
8) PAY REINSPECTION FEE BEFORE NEXT INSPECTION

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW