Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/16/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/25/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS AND EMT TO COMPLETELY SEAL INTO CONDUCTORS AND COUPLINGS
2) EQUIPMENT GROUNDS AND NEUTRALS TO BE SEPERATE AT SUB PANEL
3) CONNECT EQUIPMENT GROUND BAR TO PANEL ENCLOSURE AT SUB PANEL
4) SEAL OPENING AT WIRE ENTRY WITH NON COMBUSTIBLE MATERIAL AT BACK OF SUB PANEL
5) CHECK ALL WIRE TERMINATIONS TIGHTENED PER MANUFACTURES REQUIREMENT
6) #8 AL GOOD FOR 30 AMP ONLY
7) 1 1/4" EMT NOT SIZED PROPERLY FOR 4-1/0 XHHW
8) PAY REINSPECTION FEE BEFORE NEXT INSPECTION
09/01/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/31/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/28/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) GATE LOCKED-NO ACCESS
08/27/2009 ELECTRIC - FINAL Cancelled CANCELLED PER CONTRACTOR GABE GARCIA #971-1951
08/27/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE FITTINGS
2. VERIFY DERATING ON CABLES AND CONDUCTORS 310.5, 310.16 OUTSIDE HEATING FACTOR
3. PANEL LABELING NOT DONE -- LABEL AS PER 408.4

*SIGNS ON EQUIPMENT "NOT READY"
08/19/2009 ELECTRIC - FINAL Cancelled IVRS - RI canceled
08/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*