Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
2101 E HANCOCK VISTA
Apply Date:
07/17/2009
Applicant:
DATHAN RIVERA
Description:
UPGRADE: ELECTRIC FROM 60-200 AMPS

Permit Reviews

Permit Number - T09EL01672
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC FROM 60-200 AMPS
Start Date Submittal Complete Date Status  
01/19/2010 ELECTRICAL 01/19/2010 COMPLETED Review Details
07/17/2009 ELECTRICAL 07/17/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09EL01672
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC FROM 60-200 AMPS
Total Outstanding Activity Conditions - 1
Date Name
07/17/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09EL01672
Permit Description: UPGRADE: ELECTRIC FROM 60-200 AMPS
Total Completed Inspections - 5
Date Description Inspector Results Comments
07/24/2009 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED GAS AND WATER BOND
2) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NEW COMBUSTIBLE PRODUCT
3) ONLY (1) GROUNDED CONDUCTOR PER LUG TERMINATION
4) NM CABLES TO EXTEND 1/4" INTO CABINET
5) RISER HARDWARE TO BE 1/4" MINIMUM
6) PLEASE VERIFY PERMIT FOR NEW WIRING
7) FILL UNUSED OPENING
07/24/2009 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
02/25/2010 ELECTRIC - SERVICE UPGRADE RMORENO Approved
02/26/2010 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. MORENO
06/02/2010 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None CONSTRPLANS VIEW
None DOCUMENTS VIEW