Permit: T09EL01672

Parcel: 132102490

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/25/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) ITEMS ON LIST ALL OK
07/24/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED GAS AND WATER BOND
2) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NEW COMBUSTIBLE PRODUCT
3) ONLY (1) GROUNDED CONDUCTOR PER LUG TERMINATION
4) NM CABLES TO EXTEND 1/4" INTO CABINET
5) RISER HARDWARE TO BE 1/4" MINIMUM
6) PLEASE VERIFY PERMIT FOR NEW WIRING
7) FILL UNUSED OPENING