Permit: T09EL01608
Permit Details
Apply Date:
07/08/2009
Applicant:
MAJOR ELECTRIC INC,*C
Description:
UPGRADE: ELECTRIC TO 200 AMP (APA)
Contractors:
- MAJOR ELECTRIC INC,*C
Outstanding Activity Conditions
Permit Number - T09EL01608
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC TO 200 AMP (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/08/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09EL01608
Permit Description: UPGRADE: ELECTRIC TO 200 AMP (APA)
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2009 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CLEAN SURFACE UNDER LUGS 250.12 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR AND INSTALL MAIN BONDING JUMPER 3) NEED REJECTION PINS AND FUSES 4) CONDUIT TO 2ND SUB PANEL UNDER SIZED FOR CONDUCTORS 5) NO LOADS CONNECTED AT 1ST SUB PANEL 6) 2ND SUB PANEL HIGHEST BREAKER NOT OVER 6'-7" 7) USE APPROVED LUGS 1ST SUB PANEL 8) FINISH JUNCTION BOX DOWNSTAIRS 9) FINISH #1 PREVIOUS INSPECTION |
12/31/2009 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
01/08/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER R. HOLLANDER |