Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
191 E TOOLE AV
Apply Date:
07/08/2009
Applicant:
MAJOR ELECTRIC INC,*C
Description:
UPGRADE: ELECTRIC TO 200 AMP (APA)
Contractors:
  • MAJOR ELECTRIC INC,*C

Outstanding Activity Conditions

Permit Number - T09EL01608
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC TO 200 AMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
07/08/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09EL01608
Permit Description: UPGRADE: ELECTRIC TO 200 AMP (APA)
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/31/2009 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CLEAN SURFACE UNDER LUGS 250.12
2) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR AND INSTALL MAIN BONDING JUMPER
3) NEED REJECTION PINS AND FUSES
4) CONDUIT TO 2ND SUB PANEL UNDER SIZED FOR CONDUCTORS
5) NO LOADS CONNECTED AT 1ST SUB PANEL
6) 2ND SUB PANEL HIGHEST BREAKER NOT OVER 6'-7"
7) USE APPROVED LUGS 1ST SUB PANEL
8) FINISH JUNCTION BOX DOWNSTAIRS
9) FINISH #1 PREVIOUS INSPECTION
12/31/2009 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
01/08/2010 TEP CLEARANCE - AM JWEATHER Approved ECO CLEARED PER R. HOLLANDER

Documents

File Name Document Type  
None DOCUMENTS VIEW