Permit: T09EL01608

Parcel: 117160070


Addresses:

191 E TOOLE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01608

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2011 ELECTRIC - FINAL Approved
01/07/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #2 & 9 PREVIOUS INSPECTION
2) RECALL AFTER CROSSOVER
12/31/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CLEAN SURFACE UNDER LUGS 250.12
2) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR AND INSTALL MAIN BONDING JUMPER
3) NEED REJECTION PINS AND FUSES
4) CONDUIT TO 2ND SUB PANEL UNDER SIZED FOR CONDUCTORS
5) NO LOADS CONNECTED AT 1ST SUB PANEL
6) 2ND SUB PANEL HIGHEST BREAKER NOT OVER 6'-7"
7) USE APPROVED LUGS 1ST SUB PANEL
8) FINISH JUNCTION BOX DOWNSTAIRS
9) FINISH #1 PREVIOUS INSPECTION
09/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOND SERVICES 250.58
2) SECURE ALL GROUNDING CONDUCTORS TO STRUCTURE
3) NEED WATER BOND
4) FINISH #2
5) VERIFY WITH TEP FOR USE OF ALL IN ONE