Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01608
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2011 | ELECTRIC - FINAL | Approved | ||
01/07/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #2 & 9 PREVIOUS INSPECTION 2) RECALL AFTER CROSSOVER |
|
12/31/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CLEAN SURFACE UNDER LUGS 250.12 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR AND INSTALL MAIN BONDING JUMPER 3) NEED REJECTION PINS AND FUSES 4) CONDUIT TO 2ND SUB PANEL UNDER SIZED FOR CONDUCTORS 5) NO LOADS CONNECTED AT 1ST SUB PANEL 6) 2ND SUB PANEL HIGHEST BREAKER NOT OVER 6'-7" 7) USE APPROVED LUGS 1ST SUB PANEL 8) FINISH JUNCTION BOX DOWNSTAIRS 9) FINISH #1 PREVIOUS INSPECTION |
|
09/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND SERVICES 250.58 2) SECURE ALL GROUNDING CONDUCTORS TO STRUCTURE 3) NEED WATER BOND 4) FINISH #2 5) VERIFY WITH TEP FOR USE OF ALL IN ONE |