Permit: T09EL01533
Permit Details
Apply Date:
06/25/2009
Applicant:
THOMAS GARCIA
Description:
RECONNECT: ELECTRIC
Outstanding Activity Conditions
Permit Number - T09EL01533
Permit Status: Closed
Permit Description: RECONNECT: ELECTRIC
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/25/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T09EL01533
Permite Description: RECONNECT: ELECTRIC
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
ELECTRIC - FINAL | N/A | Not Inspected | ||
06/29/2009 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE EQUIPMENT TO BE LABELED BY ADDRESS AND UNIT NUMBERS (METAL LABELS) 2) NEED 12'-0" CLEARNACE, OVERHEAD CONDUCTORS TO GROUND 3) SERVICE TO BE GROUNDED AT METER TWO GROUND RODS, ONE AT SUB-PANEL 4) NEED GROUND TERMINAL INSTALLED AT SUB PANEL 5) NEED TO HAVE A MAX BREAKER OF 60 AMPS AT SUB PANEL 6) PLEASE OPEN SUB-PANEL INSIDE HOUSE 7) LABEL ALL CIRCUITS |