Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T09EL01533
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE EQUIPMENT TO BE LABELED BY ADDRESS AND UNIT NUMBERS (METAL LABELS) 2) NEED 12'-0" CLEARNACE, OVERHEAD CONDUCTORS TO GROUND 3) SERVICE TO BE GROUNDED AT METER TWO GROUND RODS, ONE AT SUB-PANEL 4) NEED GROUND TERMINAL INSTALLED AT SUB PANEL 5) NEED TO HAVE A MAX BREAKER OF 60 AMPS AT SUB PANEL 6) PLEASE OPEN SUB-PANEL INSIDE HOUSE 7) LABEL ALL CIRCUITS |
|
06/26/2009 | ELECTRIC - RECONNECT | Cancelled | IVRS - RI canceled |