Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T09EL01123
Permit Details
Apply Date:
05/12/2009
Applicant:
BROCKETT ELECTRIC ,
Description:
NEW 800 AMP ELECTRIC SERVICE WITH 3 REMOTE SUB-PANELS
Contractors:
- BROCKETT ELECTRIC ,
Permit Reviews
Permit Number - T09EL01123
Permit Status: Void
Permit Description: NEW 800 AMP ELECTRIC SERVICE WITH 3 REMOTE SUB-PANELS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/12/2009 | ELECTRICAL | 05/12/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09EL01123
Permit Status: Void
Permit Description: NEW 800 AMP ELECTRIC SERVICE WITH 3 REMOTE SUB-PANELS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/12/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Void
Permit Number: T09EL01123
Permite Description: NEW 800 AMP ELECTRIC SERVICE WITH 3 REMOTE SUB-PANELS
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - FINAL | N/A | Not Inspected | ||
| 07/02/2009 | ELECTRIC - UFER | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 07/02/2009 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* 1) OK 2-3" PVC TO ARENA 2) GROUNDING ELECTRODE CONDUCTOR TO CONNECT TO REBAR IN BOTTOM OF FOOTING 3) INSTALL GROUND CLAMP LISTED FOR DIRECT BURY AND FOR USE ON REBAR 4) DO NOT POUR FOOTING UNTIL UFER IS APPROVED |