Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T09EL01123
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 2-3" PVC TO ARENA 2) GROUNDING ELECTRODE CONDUCTOR TO CONNECT TO REBAR IN BOTTOM OF FOOTING 3) INSTALL GROUND CLAMP LISTED FOR DIRECT BURY AND FOR USE ON REBAR 4) DO NOT POUR FOOTING UNTIL UFER IS APPROVED |
|
| 05/14/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1-2 1/2 PVC FROM NEW SERVICE TO EXISTING HOUSE 2) OK 1-2 1/2 PVC FROM NEW SERVICE TO EXISTING BARN 3) OK 203" PVC FROM NEW SERVICE TO BOTTOM OF HILL 4) GROUND CLAMPS TO BE LISTED FOR USE ON GROUND RODS AND LISTED & MARKED FOR DIRECT BURY 5) ENSURE PANELS AT BLDGS HAVE MAIN BREAKERS PER PLANS AND NEC 225 6) ALL NEW SERVICES TO BE UNDERGROUND UNLESS WAIVER OBTAINED |