Permit: T09EL01088
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
1101 S MAGNOLIA AV
Address NEW:
1101 S MAGNOLIA AV
Apply Date:
05/07/2009
Applicant:
BLIZZARD BOB
Description:
upgrade to 200 amp overhead service
Contractors:
- ELECTRICAL WIZARD
Outstanding Activity Conditions
Permit Number - T09EL01088
Permit Status: Expired
Permit Description: upgrade to 200 amp overhead service
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/07/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09EL01088
Permite Description: upgrade to 200 amp overhead service
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2009 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDUCTORS #4 OR LARGER TO BE PROTECTED WITH PLASTIC BUSHING AND CONNECTORS 2) INSTALL CIRCUIT AND RECEPT FOR DRYER. 4 WIRE CIRCUIT IS REQUIRED. NEED PROPER OVER CURRENT PROTECTION 3) MISSING DEAD FRONT ON PANEL IN CLOSET. HOW ARE THESE PANELS IN CLOSET WIRED ? DO NOT HAVE PROPER WORKING CLEARANCES 4) COMPLETE PREVIOUS INSPECTION ITEMS 5) LABEL BREAKERS 6) NEED PROPER OVER CURRENT PROTECTION FOR #4'S TO SUB PANEL |
Completed Inspections
Permit Status: Expired
Permit Number: T09EL01088
Permit Description: upgrade to 200 amp overhead service
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. JIROUDEK |