Permit: T09EL01088

Parcel: 128141400


Addresses:

1101 S MAGNOLIA AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/13/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDUCTORS #4 OR LARGER TO BE PROTECTED WITH PLASTIC BUSHING AND CONNECTORS
2) INSTALL CIRCUIT AND RECEPT FOR DRYER. 4 WIRE CIRCUIT IS REQUIRED. NEED PROPER OVER CURRENT PROTECTION
3) MISSING DEAD FRONT ON PANEL IN CLOSET. HOW ARE THESE PANELS IN CLOSET WIRED ? DO NOT HAVE PROPER WORKING CLEARANCES
4) COMPLETE PREVIOUS INSPECTION ITEMS
5) LABEL BREAKERS
6) NEED PROPER OVER CURRENT PROTECTION FOR #4'S TO SUB PANEL
11/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) EXPOSE GROUND RODS TO BE MINIMUM 6' APART
2) BOND GAS PIPING ABOVE LOCATED PIPE
3) OK WATER BOND
4) RECALL AFTER SWING OVER COMPLETE