Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDUCTORS #4 OR LARGER TO BE PROTECTED WITH PLASTIC BUSHING AND CONNECTORS 2) INSTALL CIRCUIT AND RECEPT FOR DRYER. 4 WIRE CIRCUIT IS REQUIRED. NEED PROPER OVER CURRENT PROTECTION 3) MISSING DEAD FRONT ON PANEL IN CLOSET. HOW ARE THESE PANELS IN CLOSET WIRED ? DO NOT HAVE PROPER WORKING CLEARANCES 4) COMPLETE PREVIOUS INSPECTION ITEMS 5) LABEL BREAKERS 6) NEED PROPER OVER CURRENT PROTECTION FOR #4'S TO SUB PANEL |
|
| 11/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EXPOSE GROUND RODS TO BE MINIMUM 6' APART 2) BOND GAS PIPING ABOVE LOCATED PIPE 3) OK WATER BOND 4) RECALL AFTER SWING OVER COMPLETE |