Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
6317 E CALLE HERCULO
Apply Date:
04/28/2009
Applicant:
KIDD RANDALL
Description:
upgrade electric service to 200 amps
Contractors:
  • HANDY RANDY ELECTRIC

Outstanding Activity Conditions

Permit Number - T09EL01008
Permit Status: Expired
Permit Description: upgrade electric service to 200 amps
Total Outstanding Activity Conditions - 1
Date Name
04/28/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09EL01008
Permite Description: upgrade electric service to 200 amps
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/29/2009 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MASTED BRACING. CANNOT USE MINERALLAC STRAP
2. SEAL OPENING IN BACK OF PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE MATERIAL
3. WASHER CIRCUIT ON 20 AMP. CIRCUIT WITH #12 LEAVING PANEL BUT CONNECTS TO #14 WIRE IN UTILITY RM. NEEDS TO BE ON 15 AMP CIRCUIT
4. HAVE GROUNDED RECEPTS THROUGHOUT HOUSE ON UNGROUNDED SYSTEM
5. BATHROOM RECEPTS TO BE GFI PROTECTED
6. KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED
7. INSTALL SMOKE DETECTORS IN BEDROOMS AND HALL PER INSTRUCTIONS.

Documents

File Name Document Type  
None DOCUMENTS VIEW