Permit: T09EL01008

Parcel: 135023590

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MASTED BRACING. CANNOT USE MINERALLAC STRAP
2. SEAL OPENING IN BACK OF PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE MATERIAL
3. WASHER CIRCUIT ON 20 AMP. CIRCUIT WITH #12 LEAVING PANEL BUT CONNECTS TO #14 WIRE IN UTILITY RM. NEEDS TO BE ON 15 AMP CIRCUIT
4. HAVE GROUNDED RECEPTS THROUGHOUT HOUSE ON UNGROUNDED SYSTEM
5. BATHROOM RECEPTS TO BE GFI PROTECTED
6. KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED
7. INSTALL SMOKE DETECTORS IN BEDROOMS AND HALL PER INSTRUCTIONS.