Permit: T09EL00603
Permit Details
Apply Date:
03/20/2009
Applicant:
TODD SNEED
Description:
UPGRADE: ELECTRIC FROM 200-240 AMPS
Outstanding Activity Conditions
Permit Number - T09EL00603
Permit Status: Expired
Permit Description: UPGRADE: ELECTRIC FROM 200-240 AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/20/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09EL00603
Permite Description: UPGRADE: ELECTRIC FROM 200-240 AMPS
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2009 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MARK SERVICE DISCONNECT 2) INSTALL NEW GROUNDING ELECTRODE SYSTEM 3) BOND GAS AND WATER PIPING 4) NEED PANEL DIRECTORY 5) BOND OFF SET NIPPLE AND SERVICE RISER. SEE NEC 250.92 6) METAL RACEWAYS TO BE ELECTRICALLY CONTINOUS TO PANEL 7) INSTALL LOCK NUTS ON CONNECTORS 8) INSTALL BREAKERS LISTED FOR USE IN CUTLER-HAMMER PANEL |
| 09/28/2009 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |