Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
2330 S BONANZA AV
Apply Date:
03/20/2009
Applicant:
TODD SNEED
Description:
UPGRADE: ELECTRIC FROM 200-240 AMPS

Outstanding Activity Conditions

Permit Number - T09EL00603
Permit Status: Expired
Permit Description: UPGRADE: ELECTRIC FROM 200-240 AMPS
Total Outstanding Activity Conditions - 1
Date Name
03/20/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09EL00603
Permite Description: UPGRADE: ELECTRIC FROM 200-240 AMPS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
09/28/2009 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MARK SERVICE DISCONNECT
2) INSTALL NEW GROUNDING ELECTRODE SYSTEM
3) BOND GAS AND WATER PIPING
4) NEED PANEL DIRECTORY
5) BOND OFF SET NIPPLE AND SERVICE RISER. SEE NEC 250.92
6) METAL RACEWAYS TO BE ELECTRICALLY CONTINOUS TO PANEL
7) INSTALL LOCK NUTS ON CONNECTORS
8) INSTALL BREAKERS LISTED FOR USE IN CUTLER-HAMMER PANEL
09/28/2009 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*

Documents

File Name Document Type  
None DOCUMENTS VIEW