2330 S BONANZA AV

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/28/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MARK SERVICE DISCONNECT
2) INSTALL NEW GROUNDING ELECTRODE SYSTEM
3) BOND GAS AND WATER PIPING
4) NEED PANEL DIRECTORY
5) BOND OFF SET NIPPLE AND SERVICE RISER. SEE NEC 250.92
6) METAL RACEWAYS TO BE ELECTRICALLY CONTINOUS TO PANEL
7) INSTALL LOCK NUTS ON CONNECTORS
8) INSTALL BREAKERS LISTED FOR USE IN CUTLER-HAMMER PANEL
05/04/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER NOTE BY HOMEOWNER