Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MARK SERVICE DISCONNECT 2) INSTALL NEW GROUNDING ELECTRODE SYSTEM 3) BOND GAS AND WATER PIPING 4) NEED PANEL DIRECTORY 5) BOND OFF SET NIPPLE AND SERVICE RISER. SEE NEC 250.92 6) METAL RACEWAYS TO BE ELECTRICALLY CONTINOUS TO PANEL 7) INSTALL LOCK NUTS ON CONNECTORS 8) INSTALL BREAKERS LISTED FOR USE IN CUTLER-HAMMER PANEL |
|
| 05/04/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER NOTE BY HOMEOWNER |