Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2100 E 18TH ST
Address NEW:
2100 E 18TH ST
Apply Date:
02/11/2009
Applicant:
GEFTER BORIS
Description:
Electrical Panel Repair; BUSS & BREAKER
Contractors:
  • A AMERICAN ELECTRICAL SERVICES

Outstanding Activity Conditions

Permit Number - T09EL00260
Permit Status: Expired
Permit Description: Electrical Panel Repair; BUSS & BREAKER
Total Outstanding Activity Conditions - 1
Date Name
02/11/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09EL00260
Permite Description: Electrical Panel Repair; BUSS & BREAKER
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/06/2009 ELECTRIC - FINAL N/A Denied 1) WORK BY A-AMERICAN OK AND APPROVED
2) OWNER OF PROPERTY NOTICE:
NOTE THAT NEW UNDERGROUND FEEDERS TO APTS NOT TO CODE, NOT PERMITED. WIRE NOT LISTED FOR UNDERGROUND USE, CONDUIT TO SHALLOW, ONLY 6" DEEP, NO GROUNDING ELECTRODE SYSTEM AT OTHER BLDGS, OBTAIN PERMITS FOR UNITS, ELECTRICAL UPGRADES WITH APPROVED PLANS
3) THIS WILL BE TURNED OVER TO DEPT OF NEIGHBOR HOOD RESOURCES

Completed Inspections

Permit Status: Expired
Permit Number: T09EL00260
Permit Description: Electrical Panel Repair; BUSS & BREAKER
Total Completed Inspections - 3
Date Description Inspector Results Comments
02/12/2009 TEP CLEARANCE - PM BFLORES Approved RECN PER D.SANTA CRUZ
(CLEAR UNITS #2100, #2102, #2106 AND #2108)
03/06/2009 ELECTRIC - SERVICE UPGRADE DSANTACR Approved IVRS - Inspection :*
03/09/2009 TEP CLEARANCE - AM JWEATHER Approved RECN CLEARED PER D. SANTACRUZ

Documents

File Name Document Type  
None DOCUMENTS VIEW