Permit: T09EL00260

Parcel: 129053290


Addresses:

2100 E 18TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/06/2009 ELECTRIC - FINAL Denied 1) WORK BY A-AMERICAN OK AND APPROVED
2) OWNER OF PROPERTY NOTICE:
NOTE THAT NEW UNDERGROUND FEEDERS TO APTS NOT TO CODE, NOT PERMITED. WIRE NOT LISTED FOR UNDERGROUND USE, CONDUIT TO SHALLOW, ONLY 6" DEEP, NO GROUNDING ELECTRODE SYSTEM AT OTHER BLDGS, OBTAIN PERMITS FOR UNITS, ELECTRICAL UPGRADES WITH APPROVED PLANS
3) THIS WILL BE TURNED OVER TO DEPT OF NEIGHBOR HOOD RESOURCES
02/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*