Permit Details

Status:
Si_xpire
Type:
SINGLE FAMILY ADDITION
Address:
6181 E 4TH ST
Address NEW:
6181 E 4TH ST
Apply Date:
12/01/2009
Applicant:
N/A
Description:
SOLAR WATER HEATER:UPGRADE ELECTRIC
Contractors:
  • RUSSETT SERVICE CORPORATION, *C

Permit Reviews

Permit Number - T09CM03153
Permit Status: Si_xpire
Permit Description: SOLAR WATER HEATER:UPGRADE ELECTRIC
Start Date Submittal Complete Date Status  
01/21/2010 REVISION - - 1ST 06/10/2010 COMPLETED Review Details
12/01/2009 PLANS OK TO SUBMIT - RES 12/10/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM03153
Permit Status: Si_xpire
Permit Description: SOLAR WATER HEATER:UPGRADE ELECTRIC
Total Outstanding Activity Conditions - 3
Date Name
12/01/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
12/01/2009 SPECIAL INSPECTION FORMS AND REPORTS REQUIRED PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY.
12/01/2009 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.

Completed Inspections

Permit Status: Si_xpire
Permit Number: T09CM03153
Permit Description: SOLAR WATER HEATER:UPGRADE ELECTRIC
Total Completed Inspections - 5
Date Description Inspector Results Comments
12/16/2009 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE ELETRICAL INSPECTION ADDED TO THIS PERMIT CARD FOR NEW ELECTRIC CIRCUIT
2) PROVIDE GREEN WIRE FOR GROUND CIRCUIT
3) HOT & COLD POTABLE WATER PIPING RE-ROUTED TO WATER HEATER LOCATION TO BE INSULATED PROPERLY, JOINTS SEALED AND INSULATION PROTECTED FROM SUNLIGHT DAMAGE
4) PANEL AND PANEL PIPING SHALL BE ELEVATED MINIMUM 1 1/2" ABOVE ROOF SURFACE
5) ALL J-HOOKS DRIVEN DIRECTLY INTO ROOF TO BE REMOVED AND HOLES PATCHED
6) PIPING FOR PANEL IS NOT GRAVITY DRAIN BACK TO DRAIN BACK TANK AS REQUIRED
7) NORTH EXPOSURE OF THE SOLAR PANEL IS NOT TYPICAL INSTALLATION
8) LOW VOLTAGE SENSORE WIRE SHALL BE PROTECTED FROM DAMAGE
9) INSULATE HOT PIPING FROM DRAIN BACK TANK EXCHANGER TO AVOID POSSIBILITY OF BURNS TO CHILDREN
12/16/2009 PLUMBING - FINAL RRICH Approved IVRS - Inspection :
See detailed listing on site.| 999*
03/23/2010 ELECTRIC - SERVICE UPGRADE RRICH Approved IVRS - Inspection :*
03/23/2010 ELECTRIC - INTERMEDIATE RRICH Approved IVRS - Inspection :*
06/12/2010 ELECTRIC - FINAL RFREIDIN Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW