Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address:
2600 N WYATT DR
Apply Date:
10/15/2009
Applicant:
N/A
Description:
TI: MEDICAL OFFICE
Architects:
  • JONES BRUCE
Contractors:
  • BARKER MORRISSEY CONTRACTING INC **C

Permit Reviews

Permit Number - T09CM02767
Permit Status: Final
Permit Description: TI: MEDICAL OFFICE
Start Date Submittal Complete Date Status  
10/15/2009 COMMERCIAL TI 10/20/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM02767
Permit Status: Final
Permit Description: TI: MEDICAL OFFICE
Total Outstanding Activity Conditions - 1
Date Name
10/15/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09CM02767
Permit Description: TI: MEDICAL OFFICE
Total Completed Inspections - 19
Date Description Inspector Results Comments
11/25/2009 ELECTRIC - INTERMEDIATE RMORENO Approved IVRS - Inspection :*
1) WALL IN BLDG OK
11/30/2009 FRAMING GDABBS Approved IVRS - Inspection :*
1) FRAMING AT ROLL UP DOOR
12/02/2009 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
12/03/2009 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :*
12/04/2009 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
12/09/2009 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
12/10/2009 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
12/10/2009 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
12/17/2009 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
1) OK TO SET CEILING TILES
12/17/2009 ELECTRIC - ABOVE CEILING RJIROUDE Approved IVRS - Inspection :*
1) RELOCATED LIGHT FIXTURES TO BE SECURED TO CEILING GRID
2) BOXES TO BE SUPPORTED AND SECURED
3) RACEWAYS TO BE SUPPORTED AND SEDURED WITHIN 3' OF BOXES
4) OK CEILING ROOMS 1615,1610 AND 1609
12/30/2009 ELECTRIC - FINAL RMORENO Approved IVRS - Inspection :*
1. NEED EXIT LIGHT CIRCUIT ON PANEL SCHEDULE
2. NEED TO SEE GFCI'S EXAM 1, 2, 3, 4, 6, 7, & VITALS ROOM
3. NEED HOSPITAL GRADE OUTLETS IN EXAM ROOMS
12/30/2009 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
12/30/2009 PLUMBING - PROGRESS BBENEDON Approved IVRS - Inspection :*
12/30/2009 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
12/30/2009 FIRE SPKLR - FINAL LTHOMAS Approved Partial Sprinkler Final in Area D,E,F only.
12/30/2009 FIRE - FINAL LTHOMAS Approved Partial CofO
01/04/2010 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) OK FOR FINAL
01/07/2010 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
01/07/2010 BUILDING - PROGRESS JBURGE Approved IVRS - Inspection :*