Permit: T09CM02265
Permit Details
Apply Date:
08/25/2009
Applicant:
N/A
Description:
GAS PACK:REPLACEMENT
Contractors:
- OASIS AIR CONDITIONING AND HEATI
Permit Reviews
Permit Number - T09CM02265
Permit Status: Expired
Permit Description: GAS PACK:REPLACEMENT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/25/2009 | OTHER | 09/03/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09CM02265
Permit Status: Expired
Permit Description: GAS PACK:REPLACEMENT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/25/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09CM02265
Permite Description: GAS PACK:REPLACEMENT
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PLUMBING - GAS PRESSURE TEST | N/A | Not Inspected | ||
| MECHANICAL - INTERMEDIATE | N/A | Not Inspected | ||
| 09/14/2009 | PLUMBING - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) SUPPORT HORIZONTAL PVC EVERY 4' 2) USE PURPLE PRIMER PRIOR TO GLUING FITTINGS 3) PAINT EXPOSED PVC WITH LATEX PAINT 4) ZIP TIES NOT APPROVED FOR HANGERS 5) INSULATE SHEET METAL DUCT FITTINGS IN ATTIC WITH R8 AND PROVIDE R8 FLEX DUCTS 6) SECURE ELECTRIC DISCONNECT ON ROOF 7) SECURE GAS PIPE IN ATTIC |
Completed Inspections
Permit Status: Expired
Permit Number: T09CM02265
Permit Description: GAS PACK:REPLACEMENT
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2009 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |