Start Date Submittal Complete Date Status  
08/25/2009 OTHER 09/03/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM02265
Permit Status: Expired
Permit Description: GAS PACK:REPLACEMENT
Total Outstanding Activity Conditions - 1
Date Name
08/25/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09CM02265
Permite Description: GAS PACK:REPLACEMENT
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
PLUMBING - GAS PRESSURE TEST N/A Not Inspected
MECHANICAL - INTERMEDIATE N/A Not Inspected
09/14/2009 PLUMBING - FINAL N/A Partial Approval IVRS - Inspection :*
1) SUPPORT HORIZONTAL PVC EVERY 4'
2) USE PURPLE PRIMER PRIOR TO GLUING FITTINGS
3) PAINT EXPOSED PVC WITH LATEX PAINT
4) ZIP TIES NOT APPROVED FOR HANGERS
5) INSULATE SHEET METAL DUCT FITTINGS IN ATTIC WITH R8 AND PROVIDE R8 FLEX DUCTS
6) SECURE ELECTRIC DISCONNECT ON ROOF
7) SECURE GAS PIPE IN ATTIC

Completed Inspections

Permit Status: Expired
Permit Number: T09CM02265
Permit Description: GAS PACK:REPLACEMENT
Total Completed Inspections - 1
Date Description Inspector Results Comments
09/22/2009 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW