Description:
CODE COMPLIANCE: ADDITION:LIVING ROOM/BEDROOM & BATHROOM R1 ADD PLUMBING REPAIRS TO REAR BATHROOM
Contractors:
  • CATALINA CUSTOM CONSTRUCTION*C
  • FITZGERALD AND SONS

Permit Reviews

Permit Number - T09CM00721
Permit Status: Expired
Permit Description: CODE COMPLIANCE: ADDITION:LIVING ROOM/BEDROOM & BATHROOM R1 ADD PLUMBING REPAIRS TO REAR BATHROOM
Start Date Submittal Complete Date Status  
03/31/2009 RESIDENTIAL BLDG/ZONING/ENGINE/WWM 06/17/2009 COMPLETED Review Details
06/17/2009 REVISION - - 1ST 06/17/2009 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T09CM00721
Permit Status: Expired
Permit Description: CODE COMPLIANCE: ADDITION:LIVING ROOM/BEDROOM & BATHROOM R1 ADD PLUMBING REPAIRS TO REAR BATHROOM
Total Outstanding Activity Conditions - 1
Date Name
03/31/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T09CM00721
Permite Description: CODE COMPLIANCE: ADDITION:LIVING ROOM/BEDROOM & BATHROOM R1 ADD PLUMBING REPAIRS TO REAR BATHROOM
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
07/18/2009 PLUMBING - INTERMEDIATE N/A Partial Approval 1) SEWER LINE INSTALLED, AT REAR OF HOUSE 1ST 90 DEGREE FITTING IS SANITARY 1/4" BEND, MUST BE A 90 DEGREE SWEEP
2) SOIL LINES IN BATHROOM OK, HCS SEWER OK NEED APPROVED PLAN
3) FTGS ARE 16" WIDE 12" PLUS DEEP TWO HORIZONTAL #4'S
07/18/2009 PLUMBING - SEWER HCS CONNECT N/A Partial Approval
07/20/2009 PLUMBING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BEDROOM AND SMOKE DETECTORS TO BE ON ARC FAULT BREAKERS
2) GFCI RECEPTACLE TO FAR FROM LAV.
3) SHOWER COMPARTMENT TILE TO BE ON CEMENT BACKER BOARD, FLOOR TO BE H20 TIGHT
4) MISSING LIGHT FIXTURE BATHROOM
5) LOOSE WALL RECEPTS EAST BEDROOM
6) NEED SEPERATE CIRCUIT WALL A/C
7) NEED ACCESS TO ATTIC UNIT, LABEL BREAKER IN SERVICE PANEL
8) EXHAUST FAN COVER
9) ISOLATE NEUTRALS AND GRDS IN SUB PANEL
9) VERIFY PLUMBING VENTS THRU ROOF

Completed Inspections

Permit Status: Expired
Permit Number: T09CM00721
Permit Description: CODE COMPLIANCE: ADDITION:LIVING ROOM/BEDROOM & BATHROOM R1 ADD PLUMBING REPAIRS TO REAR BATHROOM
Total Completed Inspections - 2
Date Description Inspector Results Comments
09/09/2009 BUILDING - PROGRESS DQUINN Approved
09/09/2009 BUILDING - FINAL DQUINN Approved IVRS - Inspection :*

Documents