Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BEDROOM AND SMOKE DETECTORS TO BE ON ARC FAULT BREAKERS 2) GFCI RECEPTACLE TO FAR FROM LAV. 3) SHOWER COMPARTMENT TILE TO BE ON CEMENT BACKER BOARD, FLOOR TO BE H20 TIGHT 4) MISSING LIGHT FIXTURE BATHROOM 5) LOOSE WALL RECEPTS EAST BEDROOM 6) NEED SEPERATE CIRCUIT WALL A/C 7) NEED ACCESS TO ATTIC UNIT, LABEL BREAKER IN SERVICE PANEL 8) EXHAUST FAN COVER 9) ISOLATE NEUTRALS AND GRDS IN SUB PANEL 9) VERIFY PLUMBING VENTS THRU ROOF |
|
| 07/07/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL OK EXCEPT REAR BIB-CANNOT BE PVC ABOVE GROUND AND NEEDS BACKFLOW PREVENTER |