Permit: T09BU01653
Permit Details
Apply Date:
11/06/2009
Applicant:
CINTAS FIRE PROTECTION
Description:
HOOD INSTALL
Contractors:
- CINTAS FIRE PROTECTION
Permit Reviews
Permit Number - T09BU01653
Permit Status: Final
Permit Description: HOOD INSTALL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/06/2009 | MECHANICAL | 11/06/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09BU01653
Permit Status: Final
Permit Description: HOOD INSTALL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/06/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09BU01653
Permit Description: HOOD INSTALL
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2009 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) HOOD IS NOT OF TYPE I CONSTRCUTION GALV. CONSTRUCTION SCREWED/PITTS JOINTS AND SEAMS 2) GREASE DUCT NOT TYPE 1 CONSTRUCTION GALV. PITTSBURGH CONSTRUCTION WITHOUT CLEARANCES THRU ATTIC SPACE PRESUMED 3) FAN ON ROOF IS TYPE 1 UP BLAST BUT DUCT PENETRATES ROOF WITH 0 CLEARANCE TO COMBUSTIBLE MATERIALS 4) THIS SYSTEM HAS APPROX. 35'-40' OF HORIZONTAL GREASE DUCT WITH NO CLEANOUTS. THIS SYSTEM SHOULD BE OPENED AND CLEANED IMMEDIATELY TO REDUCE ANY RISK OF GREASE FIRE |
| 03/02/2010 | FIRE - KITCHEN EXH HOOD FINAL | DSIWARSKI | Approved | Approved |