Inspection History: MECHANICAL - FINAL

Permit Number - T09BU01653

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/01/2010 MECHANICAL - FINAL Approved TWO EACH CLEAN-OUTS INSTALLED ALONG HORIZONTAL SECTION OF DUCT. ACCESS PANELS INSTALLED IN CEILING TO REACH CLEAN-OUTS. DUCT CLEANED AND IN GOOD SHAPE.
01/28/2010 MECHANICAL - FINAL Partial Approval SITE HAS BEEN REVISITED BY LEE RAY HANLY AND ROBERT SHERRY(P.E.).

HOOD AND DUCT MEET STANDARDS ADOPTED AT TIME OF INSTALLATION. I.E. GALVANIZED STEEL WITH GREASE-TIGHT SEAMS BRAZED ON OUTSIDE.

THERE ARE NO CURRENT CLEAN OUT PORTS SO THERE NEEDS TO BE SOME EVIDENCE OF ABILITY TO CLEAN HORIZONTAL SECTION AS IS...OR THE INSTALLATION OF CLEAN OUT PORTS WILL BE REQUIRED.
11/13/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOOD IS NOT OF TYPE I CONSTRCUTION GALV. CONSTRUCTION SCREWED/PITTS JOINTS AND SEAMS
2) GREASE DUCT NOT TYPE 1 CONSTRUCTION GALV. PITTSBURGH CONSTRUCTION WITHOUT CLEARANCES THRU ATTIC SPACE PRESUMED
3) FAN ON ROOF IS TYPE 1 UP BLAST BUT DUCT PENETRATES ROOF WITH 0 CLEARANCE TO COMBUSTIBLE MATERIALS
4) THIS SYSTEM HAS APPROX. 35'-40' OF HORIZONTAL GREASE DUCT WITH NO CLEANOUTS. THIS SYSTEM SHOULD BE OPENED AND CLEANED IMMEDIATELY TO REDUCE ANY RISK OF GREASE FIRE