Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
11/06/2009
Applicant:
CINTAS FIRE PROTECTION
Description:
HOOD INSTALL
Contractors:
  • CINTAS FIRE PROTECTION

Permit Reviews

Permit Number - T09BU01653
Permit Status: Final
Permit Description: HOOD INSTALL
Start Date Submittal Complete Date Status  
11/06/2009 MECHANICAL 11/06/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09BU01653
Permit Status: Final
Permit Description: HOOD INSTALL
Total Outstanding Activity Conditions - 1
Date Name
11/06/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09BU01653
Permit Description: HOOD INSTALL
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/13/2009 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) HOOD IS NOT OF TYPE I CONSTRCUTION GALV. CONSTRUCTION SCREWED/PITTS JOINTS AND SEAMS
2) GREASE DUCT NOT TYPE 1 CONSTRUCTION GALV. PITTSBURGH CONSTRUCTION WITHOUT CLEARANCES THRU ATTIC SPACE PRESUMED
3) FAN ON ROOF IS TYPE 1 UP BLAST BUT DUCT PENETRATES ROOF WITH 0 CLEARANCE TO COMBUSTIBLE MATERIALS
4) THIS SYSTEM HAS APPROX. 35'-40' OF HORIZONTAL GREASE DUCT WITH NO CLEANOUTS. THIS SYSTEM SHOULD BE OPENED AND CLEANED IMMEDIATELY TO REDUCE ANY RISK OF GREASE FIRE
03/02/2010 FIRE - KITCHEN EXH HOOD FINAL DSIWARSKI Approved Approved