Permit: T09BU01340
Permit Details
Apply Date:
09/08/2009
Applicant:
INDEPENDENT FIRE AND SAFETY L L C
Description:
EXHAUST HOOD:
Contractors:
- INDEPENDENT FIRE AND SAFETY L L C
Permit Reviews
Permit Number - T09BU01340
Permit Status: Final
Permit Description: EXHAUST HOOD:
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/08/2009 | MECHANICAL | 09/08/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09BU01340
Permit Status: Final
Permit Description: EXHAUST HOOD:
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/08/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09BU01340
Permit Description: EXHAUST HOOD:
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2009 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) CLEANOUT ON GREASE DUCT NOT PROPERLY INSTALLED, NEEDS BOLTS, WING NUTS AND FIRE WRAP ATTACHED 2) THERE IS A HOLE CUT INTO THE SIDE OF THE HOOD WHICH NEEDS TO BE REPAIRED PROPERLY 3) THERE IS A PATCH ON THE SIDE OF THE EXHAUST FAN LEAKING GREASE AND DOES NOT FIT PROPERLY 4) NEED TO REMOVE HOOD FILTERS FOR INSPECTION ON DUCT TO HOOD CONNECTION 5) RECOMMEND A MECHANICAL CONTRACTOR DO THE REPAIRS |
| 11/10/2010 | FIRE - KITCHEN EXH HOOD FINAL | DRamirez | Approved | Approved 11/10/10 |