Permit: T09BU01340

Parcel: 11005318J


Addresses:

3001 N SWAN RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/10/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/20/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLEANOUT ON GREASE DUCT NOT PROPERLY INSTALLED, NEEDS BOLTS, WING NUTS AND FIRE WRAP ATTACHED
2) THERE IS A HOLE CUT INTO THE SIDE OF THE HOOD WHICH NEEDS TO BE REPAIRED PROPERLY
3) THERE IS A PATCH ON THE SIDE OF THE EXHAUST FAN LEAKING GREASE AND DOES NOT FIT PROPERLY
4) NEED TO REMOVE HOOD FILTERS FOR INSPECTION ON DUCT TO HOOD CONNECTION
5) RECOMMEND A MECHANICAL CONTRACTOR DO THE REPAIRS
09/17/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE APPROVED GREASE DUCT CLEANOUT ACCESS DOOR
2) TYPE 1 DUCT IS TO BE WELDED TO ?